Home / Tools / Wire gauge & fuse calculator

Marine wire gauge & fuse calculator

Size a 12 or 24 V circuit the way ABYC does: for voltage drop and for ampacity, with the larger answer winning. Then get the fuse that protects that wire, the fuse types that come in that rating, and where it has to go.

How it works

ABYC E-11 sizes every DC conductor twice. Voltage drop: circular mils = 10.75 × amps × the round-trip length in feet ÷ the volts you can afford to lose, and the next size up wins when the answer falls between two. Ampacity: the wire has to carry the current without overheating, from the Coast Guard's table for the wire's temperature rating, derated for engine spaces and bundles. The larger of the two is the minimum, never below 16 AWG. The calculator then fits a standard fuse between 125% of the load and what the wire carries; if none fits, it steps the wire up and tells you the fuse set the size.

3% or 10%?

ABYC allows 3% for panel feeders, bilge blowers, electronics and navigation lights, and 10% for other lighting and loads where a little sag doesn't matter. Ancor puts bilge pumps in the 3% group, and so do we. At 12 V, 3% is 0.36 V; at 24 V it's 0.72 V, which is why 24 V systems get away with thinner wire. (West Marine's tip to use the 10% table for 24 V critical loads is wrong: 3% at 24 V equals 6% at 12 V, not 10%.)

Where the fuse goes

A fuse protects the wire, so it sits at the source end: within 7 inches of the battery or bus, measured along the wire. ABYC stretches that to 72 inches for a wire straight off the battery terminal that's sheathed or enclosed all the way, and to 40 inches from other sources when sheathed; the Coast Guard rule for gasoline-inboard boats stops at 40. Engine cranking cables are exempt. Keep fuses and breakers out of the battery compartment itself, and for a lithium bank use a Class T main fuse for its 20,000 A interrupt rating. Our guide to powering a boat computer walks through a real install.

AWG or SAE wire?

Marine boat cable (UL 1426) is sized in AWG. Automotive SAE wire with the same number is 5 to 12% smaller in copper and carries correspondingly less. If that's what you're buying, choose SAE and the calculator sizes from the smaller areas. Wet runs in bilges should use the 75 °C column: Ancor rates its tinned boat cable 105 °C dry but 75 °C wet.

Quick reference, 12 V

Each size is the larger of what voltage drop and ampacity need, stepped up when a standard fuse wouldn't fit between 125% of the load and the wire's rating. Lengths are one way; the calculation doubles them. A dash means no single conductor up to 4/0 does it.

12 V, 3% drop: AWG by load and one-way run (105 °C boat cable, outside engine spaces, one circuit)
Load5 ft10 ft15 ft20 ft25 ft35 ft50 ft
5 A161412121088
10 A1412108864
15 A121086642
20 A12866422
30 A10644221/0
40 A8642212/0
60 A64211/02/04/0
80 A6211/02/03/0—
100 A421/02/03/04/0—
12 V, 10% drop: AWG by load and one-way run (105 °C boat cable, outside engine spaces, one circuit)
Load5 ft10 ft15 ft20 ft25 ft35 ft50 ft
5 A16161616161412
10 A16161414121210
15 A1614141210108
20 A161412101086
30 A1212108864
40 A101088664
60 A8886442
80 A6664421
100 A4444221/0

Ampacity and wire areas

Ampacity from 33 CFR 183.425 Table 5 (the Coast Guard's copy of ABYC E-11 Table IV), single conductor; engine spaces ×0.85 for 105 °C wire. Minimum circular-mil areas from ABYC E-11 (2003) Table XII. Bundles: ×0.7 for three conductors, ×0.6 for four to six, ×0.5 for seven to 24, ×0.4 above that. Checked 2026-11-12.

Wire105 °C105 °C, engine space75 °C (wet)AWG areaSAE area
16 AWG25 A21.3 A15 A2,580 CM2,336 CM
14 AWG35 A29.8 A20 A4,110 CM3,702 CM
12 AWG45 A38.3 A25 A6,530 CM5,833 CM
10 AWG60 A51 A40 A10,380 CM9,343 CM
8 AWG80 A68 A65 A16,510 CM14,810 CM
6 AWG120 A102 A95 A26,240 CM24,538 CM
4 AWG160 A136 A125 A41,740 CM37,360 CM
2 AWG210 A178.5 A170 A66,360 CM62,450 CM
1 AWG245 A208.3 A195 A83,690 CM77,790 CM
1/0 AWG285 A242.3 A230 A105,600 CM98,980 CM
2/0 AWG330 A280.5 A265 A133,100 CM125,100 CM
3/0 AWG385 A327.3 A310 A167,800 CM158,600 CM
4/0 AWG445 A378.3 A360 A211,600 CM205,500 CM

The method follows the public 2003 edition of ABYC E-11 and the Coast Guard's 33 CFR 183.425 and 183.455; ABYC's current edition is paywalled and may differ. This is a sizing aid, not a substitute for the standard or a marine electrician.

Frequently asked questions

What size wire do I need on a boat?

Size it twice and use the larger answer, as ABYC E-11 requires. First for voltage drop: circular mils = 10.75 × amps × round-trip feet ÷ allowed volts, with 3% allowed for electronics, nav lights, bilge pumps and panel feeders and 10% for other loads. Then for ampacity: the wire must carry the current after derating for engine spaces and bundles. For example, a 10 A load 15 feet from the panel at 12 V and 3% needs 10 AWG; at 10% it needs 14 AWG.

What size fuse should I use?

Size the fuse to protect the wire, not the device. Blue Sea's rule is a fuse of at least 125% of the load and no more than the wire's ampacity; ABYC and the Coast Guard allow up to 150% of the wire's ampacity under 50 V, but staying at or below the wire's rating is the safer choice. If the maker specifies a fuse or breaker, use that rating and make sure the wire can carry it.

How close to the battery does the fuse have to be?

Within 7 inches of the battery or other power source, measured along the wire. ABYC allows up to 72 inches if the wire connects directly to the battery terminal and is sheathed or enclosed all the way, and up to 40 inches from other sources when sheathed. The Coast Guard rule for gasoline-inboard boats stops at 40 inches. Engine cranking cables are exempt.

Why is this one size smaller than the ABYC table?

The calculator uses ABYC's own formula with the circular-mil areas of true AWG boat cable. ABYC's printed voltage-drop tables come out one size larger in many cells, and they match the formula almost exactly when you use the smaller SAE wire areas instead, so we believe they were built that way; ABYC doesn't say. Choose SAE in the calculator to reproduce the tables, or step up one size if you want the extra margin.

Do I need to derate wires in a bundle?

The sources disagree. The Coast Guard's rule (33 CFR 183.425) derates from three current-carrying conductors up: ×0.70 for three, ×0.60 for four to six, ×0.50 for seven to 24, ×0.40 above that. ABYC's 2003 edition didn't derate under 50 V, and a later edition appears to derate even a single duplex cable. The calculator uses the Coast Guard rule; count both wires of every circuit in the bundle.

Share