How it works
ABYC E-11 sizes every DC conductor twice. Voltage drop: circular mils = 10.75 × amps × the round-trip length in feet ÷ the volts you can afford to lose, and the next size up wins when the answer falls between two. Ampacity: the wire has to carry the current without overheating, from the Coast Guard's table for the wire's temperature rating, derated for engine spaces and bundles. The larger of the two is the minimum, never below 16 AWG. The calculator then fits a standard fuse between 125% of the load and what the wire carries; if none fits, it steps the wire up and tells you the fuse set the size.
3% or 10%?
ABYC allows 3% for panel feeders, bilge blowers, electronics and navigation lights, and 10% for other lighting and loads where a little sag doesn't matter. Ancor puts bilge pumps in the 3% group, and so do we. At 12 V, 3% is 0.36 V; at 24 V it's 0.72 V, which is why 24 V systems get away with thinner wire. (West Marine's tip to use the 10% table for 24 V critical loads is wrong: 3% at 24 V equals 6% at 12 V, not 10%.)
Where the fuse goes
A fuse protects the wire, so it sits at the source end: within 7 inches of the battery or bus, measured along the wire. ABYC stretches that to 72 inches for a wire straight off the battery terminal that's sheathed or enclosed all the way, and to 40 inches from other sources when sheathed; the Coast Guard rule for gasoline-inboard boats stops at 40. Engine cranking cables are exempt. Keep fuses and breakers out of the battery compartment itself, and for a lithium bank use a Class T main fuse for its 20,000 A interrupt rating. Our guide to powering a boat computer walks through a real install.
AWG or SAE wire?
Marine boat cable (UL 1426) is sized in AWG. Automotive SAE wire with the same number is 5 to 12% smaller in copper and carries correspondingly less. If that's what you're buying, choose SAE and the calculator sizes from the smaller areas. Wet runs in bilges should use the 75 °C column: Ancor rates its tinned boat cable 105 °C dry but 75 °C wet.
Quick reference, 12 V
| Load | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft | 35 ft | 50 ft |
|---|---|---|---|---|---|---|---|
| 5 A | 16 | 14 | 12 | 12 | 10 | 8 | 8 |
| 10 A | 14 | 12 | 10 | 8 | 8 | 6 | 4 |
| 15 A | 12 | 10 | 8 | 6 | 6 | 4 | 2 |
| 20 A | 12 | 8 | 6 | 6 | 4 | 2 | 2 |
| 30 A | 10 | 6 | 4 | 4 | 2 | 2 | 1/0 |
| 40 A | 8 | 6 | 4 | 2 | 2 | 1 | 2/0 |
| 60 A | 6 | 4 | 2 | 1 | 1/0 | 2/0 | 4/0 |
| 80 A | 6 | 2 | 1 | 1/0 | 2/0 | 3/0 | — |
| 100 A | 4 | 2 | 1/0 | 2/0 | 3/0 | 4/0 | — |
| Load | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft | 35 ft | 50 ft |
|---|---|---|---|---|---|---|---|
| 5 A | 16 | 16 | 16 | 16 | 16 | 14 | 12 |
| 10 A | 16 | 16 | 14 | 14 | 12 | 12 | 10 |
| 15 A | 16 | 14 | 14 | 12 | 10 | 10 | 8 |
| 20 A | 16 | 14 | 12 | 10 | 10 | 8 | 6 |
| 30 A | 12 | 12 | 10 | 8 | 8 | 6 | 4 |
| 40 A | 10 | 10 | 8 | 8 | 6 | 6 | 4 |
| 60 A | 8 | 8 | 8 | 6 | 4 | 4 | 2 |
| 80 A | 6 | 6 | 6 | 4 | 4 | 2 | 1 |
| 100 A | 4 | 4 | 4 | 4 | 2 | 2 | 1/0 |
Ampacity and wire areas
| Wire | 105 °C | 105 °C, engine space | 75 °C (wet) | AWG area | SAE area |
|---|---|---|---|---|---|
| 16 AWG | 25 A | 21.3 A | 15 A | 2,580 CM | 2,336 CM |
| 14 AWG | 35 A | 29.8 A | 20 A | 4,110 CM | 3,702 CM |
| 12 AWG | 45 A | 38.3 A | 25 A | 6,530 CM | 5,833 CM |
| 10 AWG | 60 A | 51 A | 40 A | 10,380 CM | 9,343 CM |
| 8 AWG | 80 A | 68 A | 65 A | 16,510 CM | 14,810 CM |
| 6 AWG | 120 A | 102 A | 95 A | 26,240 CM | 24,538 CM |
| 4 AWG | 160 A | 136 A | 125 A | 41,740 CM | 37,360 CM |
| 2 AWG | 210 A | 178.5 A | 170 A | 66,360 CM | 62,450 CM |
| 1 AWG | 245 A | 208.3 A | 195 A | 83,690 CM | 77,790 CM |
| 1/0 AWG | 285 A | 242.3 A | 230 A | 105,600 CM | 98,980 CM |
| 2/0 AWG | 330 A | 280.5 A | 265 A | 133,100 CM | 125,100 CM |
| 3/0 AWG | 385 A | 327.3 A | 310 A | 167,800 CM | 158,600 CM |
| 4/0 AWG | 445 A | 378.3 A | 360 A | 211,600 CM | 205,500 CM |
Frequently asked questions
What size wire do I need on a boat?
Size it twice and use the larger answer, as ABYC E-11 requires. First for voltage drop: circular mils = 10.75 × amps × round-trip feet ÷ allowed volts, with 3% allowed for electronics, nav lights, bilge pumps and panel feeders and 10% for other loads. Then for ampacity: the wire must carry the current after derating for engine spaces and bundles. For example, a 10 A load 15 feet from the panel at 12 V and 3% needs 10 AWG; at 10% it needs 14 AWG.
What size fuse should I use?
Size the fuse to protect the wire, not the device. Blue Sea's rule is a fuse of at least 125% of the load and no more than the wire's ampacity; ABYC and the Coast Guard allow up to 150% of the wire's ampacity under 50 V, but staying at or below the wire's rating is the safer choice. If the maker specifies a fuse or breaker, use that rating and make sure the wire can carry it.
How close to the battery does the fuse have to be?
Within 7 inches of the battery or other power source, measured along the wire. ABYC allows up to 72 inches if the wire connects directly to the battery terminal and is sheathed or enclosed all the way, and up to 40 inches from other sources when sheathed. The Coast Guard rule for gasoline-inboard boats stops at 40 inches. Engine cranking cables are exempt.
Why is this one size smaller than the ABYC table?
The calculator uses ABYC's own formula with the circular-mil areas of true AWG boat cable. ABYC's printed voltage-drop tables come out one size larger in many cells, and they match the formula almost exactly when you use the smaller SAE wire areas instead, so we believe they were built that way; ABYC doesn't say. Choose SAE in the calculator to reproduce the tables, or step up one size if you want the extra margin.
Do I need to derate wires in a bundle?
The sources disagree. The Coast Guard's rule (33 CFR 183.425) derates from three current-carrying conductors up: ×0.70 for three, ×0.60 for four to six, ×0.50 for seven to 24, ×0.40 above that. ABYC's 2003 edition didn't derate under 50 V, and a later edition appears to derate even a single duplex cable. The calculator uses the Coast Guard rule; count both wires of every circuit in the bundle.